CATEGORY: HEAT EXCHANGERS
Proceedings of International Conference on Heat
Exchanger Fouling and
Cleaning, June 9-14, 2013, Budapest, Hungary
Particulate
fouling of polymeric hollow fiber heat exchanger
I. Astrouski (1), M. Raudensky (1) and M. Dohnal
(2)
astrouski@lptap.fme.vutbr.cz
1 Heat Transfer and Flow Laboratory, Brno University of Technology, Brno, Czech
Republic
2 Center of Knowledge Economics, Brno University of Technology, Brno, Czech
Republic
Abstract
Thermal
effectiveness of heat exchangers is negatively affected by tube fouling caused
by working in contaminated conditions. Surface of polymers is smooth and
low-adhesion which provide additional antifouling resistance and defouling
possibility. Authors prepared a polymeric hollow fiber heat exchanger and
tested it to cool down water contaminated by titania particles.
Thermal performance tests showed it hight effectiveness and good
fouling resistance. it was found that the particle deposit developed rapidly
and achieved its asymptotic values during hours. It should be mentioned that
the hight rates of fouling evolution were associated with low liquid
velocities. The asymptotic (maximal) fouling level was low enough causing a
small influence on heat transfer. The associated decrease of the overall heat
transfer coefficient (HTC) was 5-20% depending on flow regimes. Moreover it was
found that particle deposit is not strong and can be easily detached and
removed from the fiber surface by local increase of liquid velocity. The
injection of air bubbles in the heat exchanger shell was tested as the
defouling procedure and showed good efficiency.